image

Refrigeration dryers are a core component of any well designed compressed air system, essential for removing the moisture that would otherwise travel downstream and damage equipment or contaminate a process. As a reliable compressed air dryer, this range is built to protect pneumatic tools, instrumentation, and production lines from the corrosion, freezing, and contamination that untreated moisture can cause. For facilities across Sri Lanka looking to round out their compressed air accessories setup with dependable air treatment, refrigeration dryers are typically the first line of defence.

The core function of a refrigeration dryer is straightforward as its compressed air is cooled to condense out water vapour, which is then separated and drained before the air continues through the system. This process of moisture removal from compressed air is critical wherever downstream equipment is sensitive to humidity, pneumatic actuators, spray finishing lines, and instrumentation air all rely on air that's been properly conditioned before use.

Performance is measured by pressure dew point, and this range achieves a pressure dew point of 2-10°C, giving operators a reliable benchmark for how dry the treated air will be under normal operating conditions. This places it firmly in the category of a genuine industrial air dryer, suited to continuous-duty environments rather than light, intermittent use.

Use cases span virtually any facility running an air compressor for production, maintenance, or process work. Manufacturing plants use an air dryer for compressed air systems to protect finishing equipment from moisture-related defects, while workshops and service centres rely on the same technology to extend the working life of pneumatic tools. Because moisture-related failures tend to be gradual and easy to overlook, a properly specified compressed air dryer often pays for itself in reduced maintenance and downtime alone.

Flexibility comes from how refrigeration dryers integrate into a wider compressed air setup. They're commonly paired with filtration and, in some applications, adsorption drying for even lower dew points, meaning this refrigeration dryer range can serve as a standalone solution or as the first stage in a more comprehensive compressed air accessories Sri Lanka businesses build around their existing compressor investment.

Technical information

The FR Series is a refrigerant-type compressed air dryer available in air-cooled (A / AP with pre-cooler) and water-cooled (W / WP with pre-cooler) configurations, with a dew point of 2-10°C across the large A/AP, W and WP model ranges, maximum operating pressure of 0.98 MPa, and refrigerant R407C (small AP models also reference R134a).

 Heat exchangers use a stainless steel shell to resist corrosion, nickel-plated brass piping for anti-corrosion protection, and a counter-flow design to extend heat exchange time and lower achievable dew point.

Segment

Model range

Capacity (m³/min, max)

Power consumption (kW)

Net weight (kg)

Small air-cooled (AP)

FR005AP–FR100AP

1.2 – 23.5

Not stated for this segment

423 – 1022

Large air-cooled (A/AP)

FR150AP–FR600A

21.4 – 79.3

4.2 – 13

460 – 1200

Water-cooled (W)

FR075W–FR3000W

10.7 – 425

2.1 – 43.17

300 – 4000

Water-cooled + pre-cooler (WP)

FR075WP–FR1000WP

10.7 – 141.4

2.4 – 16.3

260 – 1600

 

 Operating limits: ambient temperature 2-40°C; maximum air inlet temperature 45-80°C depending on type; maximum operating pressure 0.98 MPa. Sizing uses inlet-temperature and pressure correction factors (cf1, cf2) against a base flow requirement, per the manufacturer's worked examples in the source brochure.